LCB Universal Load Cells Digitizer
Universal measuring amplifier for load cells with integrated analog/digital converter
Key features
- Optional fieldbuses: PROFINET IO, Ethernet/IP, Ethernet TCP/IP,
Modbus TCP, PROFIBUS DP, EtherCAT, POWERLINK, CANopen, CC-Link, CC-Link, IE Field Basic, SERCOS III, IO-LINK - Micro USB port
- 16-bit Analog output: 0/4-20 mA; 0-5/10 V (optional)
RS485 port (optional) - Direct connection between RS485 and RS232 without converter
- 2 logic inputs, 3 relay outputs
- Single loading batchings, max 99 formulas
- Mounting: wired or integral to the load cell body via standard ¼ GAS fitting
- Suitable for wall mounting
About the LCB
Digitizer/Weight Trasmitter for load cells conceived with an eye on IoT (Internet of Things) (Internet of Things). IP67 junction box made of stainless steel AISI 316, suitable for aggressive environments. Three IP67 M12 connectors. Six indicator led of the communication interface. Dimensions: 97 x 38 x 82 mm including connectors.
LCB Digitizer transforms an analog load cell (output mV/V) into digital and can also be used on existing load cells or strain gauge sensors. Designed for an assembly/wiring integral with the load cell body, it can be connected by fieldbus to PLCs of the most important international brands.
Features LCB
- Optional fieldbuses: PROFINET IO, Ethernet/IP, Ethernet TCP/IP, Modbus TCP, PROFIBUS DP, EtherCAT, POWERLINK, CANopen, CC-Link, CC-Link, IE Field Basic, SERCOS III, IO-LINK
- Micro USB port
- 16-bit Analog output: 0/4-20 mA; 0-5/10 V (optional)RS485 port (optional)
- Direct connection between RS485 and RS232 without converter
- 2 logic inputs, 3 relay outputs
- Single loading batchings, max 99 formulas
- Mounting: wired or integral to the load cell body via standard ¼ GAS fitting
- Suitable for wall mounting
Hygienic version: LCB3A
The LCB3A variant is now also available as a measuring amplifier certified in accordance with 3-A Sanitary Standards. It has a housing made of AISI 304 stainless steel and can therefore be perfectly sanitised. LCB3A is suitable for applications in industries where hygiene is an important and indispensable requirement.
Do you need this sensor for your next project?
Request a no-obligation quote or send us your contact details for a free, no-obligation consultation. Our sales engineers will then contact you within a maximum of 1 to 2 working days.
Product downloads
Talk to our experts
Not exactly what you are looking for? We offer standard sensors, but can also help you with sensors adapted for you or a fully customised measurement solution. Contact us for advice or pricing.
Talk to an expertTechnical Specifications
Specification | Value |
---|---|
A/d converter | 24 bit (16000000 points) - 4.8 kHz |
Conversions per second | 500/s |
Decimals / display increments | 0÷4 / x1 x2 x5 x10 x20 x50 x100 |
Digital inputs | 2 - 5÷24 VDC |
Divisions (with measurement range ±10 mv and sensitivity 2 mv/v) | ±999999 / 6.6 nV/d |
Hermal drift / analog output thermal drift | <0.0005% full scale/°C / <0.003% full scale/°C |
Linearity / analog output linearity | <0.01% full scale / <0.01% full scale |
Measurement range | ±26 mV |
Micro usb port | B type - USB 2.0 (full-speed) |
Number of load cells / load cells supply | up to 4 (350 Ω) - 4/6 wires / 3.3 VDC/40 mA |
Power supply and consumption | 12÷24 VDC ±10%; 5 W |
Relay outputs | 3 - max 115 VAC/150 mA - 24 VDC/200 mA |
Usable load cells sensitivity | ±7 mV/V |